PCE-PA 8300 Three Phase Power Data Logger 3-phase / 3 current clamps / LCD graphic display / SD card memory
The PCE-PA 8300 is a Three Phase Power Data Logger that features a durable enclosure, SD card memory, a LCD graphic display, as well as apparent, effective, and reactive power measurement. The easy-to-use PCE-PA 8300 Three Phase Power Data Logger is the ideal tool for performing power and harmonics analysis as well as for measuring network capacity.
Set 2: Includes 3 flexible Rogowski coils for measurements up to 3000 A AC
Highlights
- Voltage measurement range of 10 V … 600 V AC
- Current measurement range of 30 A … 3000 A AC (Set 2)
- Performance measurement range of 0 kW … 9.999 MW (VA/VAR)
- Simultaneous display of harmonics and waveform
- Graphic Phasor diagram
- Captures transients including dip, swell, and outage
- SD card memory
- LCD graphic display
- Durable enclosure
- Compatibility with various manufacturers’ power clamps
- Adjustable back-up interval, allowing for long-term data collection
- Auto-setting of measurement range (AC V)
- Power efficiency, delay angle, and frequency measurement
- Apparent, effective, and reactive power measurement
- Harmonic spectrum measurement up to the 50th order
Technical specifications
- AC voltage — Measuring range: 10 … 600 V
- AC voltage — Accuracy: ±(0.5 % +0.5 V)
- AC voltage: Overload 720 V RMS
- Alternating current AC — Measuring range: 0,2 … 10 A
- Alternating current AC — Resolution: 0,001 A
- Alternating current AC — Accuracy: ±(0.5 % +0.1 A)
- Alternating current AC: Overload 1300 A with current clamp
- Alternating current AC — Frequency: range 40 … 1000 Hz
- Alternating current AC — Measuring range: 10 … 30 A
- Alternating current AC — Resolution: 0,01 A
- Alternating current AC — Accuracy: ±(0.5 % +0.1 A)
- Alternating current AC — Frequency: range 40 … 1000 Hz
- Alternating current AC — Measuring range: 0,2 … 100 A
- Alternating current AC — Resolution: 0,01 A
- Alternating current AC — Accuracy: ±(0.5% +0.5 A)
- Alternating current AC — Frequency: range 40 … 1000 Hz
- Alternating current AC — Measuring range: 100 … 300 A
- Alternating current AC — Resolution: 0,1 A
- Alternating current AC — Accuracy: ±(0.5% +0.5 A)
- Alternating current AC — Frequency: range 40 … 1000 Hz
- Alternating current AC — Measuring range: 0,2 … 1000 A
- Alternating current AC — Resolution: 0,1 A
- Alternating current AC — Accuracy: ±(0.5 % +5 A)
- Alternating current AC — Frequency: range 40 … 1000 Hz
- Alternating current AC — Measuring range: 1000 … 3000 A
- Alternating current AC — Resolution: 1 A
- Alternating current AC — Accuracy: ±(0.5% +5 A)
- Alternating current AC — Frequency: range 40 … 1000 Hz
- Active power — Measuring range: 0 … 9,999 kW
- Active power — Resolution: 0,001 kW
- Active power — Accuracy: ±(1 % +0.008 kW)
- Active power — Measurement range: up to 10 kW
- Active power — Measurement range: from 99,99 kW
- Active power — Resolution: 0,01 kW
- Active power — Accuracy: ±(1 % +0.008 kW) W
- Active power — Measuring range: 100 … 999,99 kW
- Active power — Resolution: 0,1 kW
- Active power — Accuracy: ±(1% +0.8 kW)
- Active power — Measuring range: 1 … 9,999 MW
- Active power — Resolution: 0,001 MW
- Active power — Accuracy: ±(1 % +0.008 MW)
- Reactive power — Measuring range: 0 … 9,99 kVAR
- Reactive power — Resolution: 0,001 kVAR
- Reactive power — Accuracy: ±(1 % +0.008 kVAR)
- Reactive power — Measuring range: 10 … 99,9 kVAR
- Reactive power — Resolution: 0,01 kVAR
- Reactive power — Accuracy: ±(1 % +0.08 kVAR)
- Reactive power — Measuring range: 100 … 999,99 kVAR
- Reactive power — Resolution: 0,1 kVAR
- Reactive power — Accuracy: ±(1 % +0.8 kVAR)
- Reactive power — Measuring range: 1 … 9,99 MVAR
- Reactive power — Resolution: 0,001 MVAR
- Reactive power — Accuracy: ±(1% +0.008 MVAR)
- Phase angle — Measuring range: -180 … +180 °
- Phase angle — Resolution: 0,1 °
- Phase angle — Accuracy: ±1 °
- Apparent power — Measuring range: 0 … 9,999 kVA
- Apparent power — Resolution: 0,001 kVA
- Apparent power — Accuracy: ±(1% +0.008 kVA)
- Apparent power — Measuring range: 10 … 99,99 kVA
- Apparent power — Resolution: 0,01 kVA
- Apparent power — Accuracy: ±(1% +0.08 kVA)
- Apparent power — Measuring range: 100 … 999,9 kVA
- Apparent power — Resolution: 0,1 kVA
- Apparent power — Accuracy: ±(1 % +0.8 kVA)
- Apparent power — Measuring range: 1 … 9,999 MVA
- Apparent power — Resolution: 0,001 MVA
- Apparent power — Accuracy: ±(1 % +0,008 MVA)
- Power factor — Measuring range: 0 … 1
- Power factor — Resolution: 0.01
- Power factor — Accuracy: ±0.04
- Active energy — Measuring range: 0 … 9,99 kWh
- Active energy — Resolution: 0,001 kWh
- Active energy — Accuracy: ±(2% +0.008 kWh)
- Active energy — Measuring range: 10 … 99,9 kWh
- Active energy — Resolution: 0,01 kWh
- Active energy — Accuracy: ±(2 % +0.08 kWh)
- Active energy — Measuring range: 100 … 999,9 kWh
- Active energy — Resolution: 0,1 kWh
- Active energy — Accuracy: ±(2 % +0.8 kWh)
- Active energy — Measuring range: 1 … 9,99 MWh
- Active energy — Resolution: 0,001 MWh
- Active energy — Accuracy: ±(2% +0.008 MWh)
- Apparent energy — Measuring range: 0 … 9,99 kVAh
- Apparent energy — Resolution: 0,001 kVAh
- Apparent energy — Accuracy: ±(2% + 0.008kVAh)
- Apparent energy — Measuring range: 10 … 99,99 kVAh
- Apparent energy — Resolution: 0,01 kVAh
- Apparent energy — Accuracy: ±(2 % +0.08 kVAh)
- Apparent energy — Measuring range: 100 … 999,9 kVAh
- Apparent energy — Resolution: 0,1 kVAh
- Apparent energy — Accuracy: ±(2% + 0.8 kVAh)
- Apparent energy — Measuring range: 1 … 9,999 MVAh
- Apparent energy — Resolution: 0,001 MVAh
- Apparent energy — Accuracy: ±(2 % +0.008 MVAh)
- Reactive energy — Measuring range: 0 … 9,99 kVArh
- Reactive energy — Resolution: 0,001 kVArh
- Reactive energy — Accuracy: ±(2% +0.008 kVARh)
- Reactive energy — Measuring range: 10 … 99,99 kVArh
- Reactive energy — Resolution: 0,01 kVArh
- Reactive energy — Accuracy: ±(2 % +0.08 kVARh)
- Reactive energy — Measuring range: 100 … 999,99 kVArh
- Reactive energy — Resolution: 0,1 kVArh
- Reactive energy — Accuracy: ±(2% +0.008 kVARh)
- Reactive energy — Measuring range: 1 … 9,99 MVARh
- Reactive energy — Resolution: 0,001 MVARh
- Reactive energy — Accuracy: ±(2% +0.008 MVARh)
- Frequency — Measuring range: 45 … 65 Hz
- Frequency — Resolution: 0,1 Hz
- Frequency — Accuracy: ±0.1 Hz
- Harmonic measurement (harmonics) — Measuring range: 1 … 50 (ordinal number)
- Harmonic measurement (harmonics): Current range 0.2 … 1200 A
- Harmonic measurement (harmonics): Voltage range 10 … 600 V
- General technical data — Measuring functions: HOLD
- General technical data — Frequency: 40 … 1000 Hz
- General technical data — Display type: LCD with backlight
- General technical data — Display size: 3,7 Inch
- Storage medium SD card — Storage capacity: 2 GB
- Storage medium SD card — Storage interval from: 2 s
- Storage medium SD card — Storage interval to: 7200 min.
- Storage medium SD card — Interface: RS232, USB
- Storage medium SD card: Standard(s)IEC 1010
- Storage medium SD card: Current consumption meter 500 mA DC
- Storage medium SD card: Current consumption current clamp 34 mA DC
- Storage medium SD card: Maximum cable diameter 175 mm
- Storage medium SD card: Safety standard CAT III 600V
- Storage medium SD card — Dimensions: Rogowski coils: 175 mm
- Storage medium SD card — Measuring range: selection Automatic, Manual
- Storage medium SD card — Menu language: English, English (GB)
- Storage medium SD card — Protection class (device): IP20
- Storage medium SD card — Power supply: 9V
- Connector type Device-europlug — (Rechargeable) battery: 8 x 1,5 V AA battery , Alkali-manganese
- Connector type Device-europlug — Capacity: 3000 mAh
- Connector type Device-europlug — Operating conditions: 0 … 50 °C , 10 … 80 % RH
- Connector type Device-europlug — Storage conditions: 0 … 50 °C , 10 … 80 % RH
- Connector type Device-europlug — Dimensions: ( L x W x H )225 x 125 x 64 mm
- Connector type Device-europlug — Weight: 1010 g
Delivery scope
- 1 x PCE-PA 8300 Portable Power Analyzer
- 3 x Flexible Rogowski coils (Set 2)
- 4 x Insulated alligator clips
- 4 x Safety test lines
- 6 x 1.5 V AA batteries
- 1 x 9 V mains adapter
- 1 x SD memory card
- 1 x Carrying case
- 1 x User manual