Power Quality Analyser / Power Analyzer for energy monitoring / configuration and data transfer via app / measurement without interrupting the power supply / incl. test leads / compact design
The Power Quality Analyser / Power Analyzer measures current and voltage values using the connected current transformers and test leads. From this, the active, apparent and reactive power are determined and transmitted to the measuring platform every second via Wi-Fi. The data is then filed historically on the Power Quality Analyser / Power Analyzer, processed graphically and can be analysed or exported. The measurement with the Power Quality Analyser / Power Analyzer is carried out using Rogowski coils or folding current transformers.
Alternatively (if no internet connection is available), the data can be recorded in the built-in 32 GB flash memory in the form of a CSV file for further processing at a later date. An SD card adaptor is also available as an accessory, which means that the recording duration is more than one year, even when recording to the second. It is also possible to send the CSV files periodically by e-mail, upload them to a server via FTP or transfer them to the measurement platform once the measurement has been completed. Interaction with the Power Quality Analyser / Power Analyzer is mainly via Wi-Fi and web browser or via app (BLE).
Power is supplied and measured via magnetic measuring tips and connection terminals or probes. The Power Quality Analyser / Power Analyzer can be connected into any main and sub-distribution board as well as into devices and systems – the power supply does not have to be interrupted. Managing the power supply is the top priority. Without measuring consumption and recording instrumental values such as current, voltage, frequency and power, it is virtually impossible to improve efficiency. The Power Quality Analyser / Power Analyzer makes it possible to monitor the entire energy consumption and helps to reduce energy costs.
Highlights
- active, apparent and reactive power
- power factor and electrical energy
- 8 MB internal memory
- app for Android
- data as CSV file
- measurement via Rogowski coils
- no additional mains connection necessary
Technical specifications
- AC voltage — Measuring range: 40 … 400 V
- AC voltage — Resolution: 0,01 V
- AC voltage — Accuracy: ±1 % of Rd
- Alternating current AC — Measuring range: 2 … 9500 A
- Alternating current AC — Resolution: 0,01 A
- Alternating current AC — Accuracy: ±1 % of Rd
- Active power — Measuring range: 80 W … 3800 kW
- Active power — Resolution: 0,01 W
- Active power — Accuracy: ±1% of Rd W
- Reactive power — Measuring range: 80 VAR … 3800 kVAR
- Reactive power — Resolution: 0,01 VAR
- Reactive power — Accuracy: ±1% of Rd
- Apparent power — Measuring range: 30 VA … 3800 kVA
- Apparent power — Resolution: 0,01 VA
- Apparent power — Accuracy: ±1% of Rd
- Power factor — Measuring range: 0 … 1
- Power factor — Resolution: 0.01
- Power factor — Accuracy: ±1 % of Rd
- General technical data: Measuring rate 26000 Hz
- Storage medium Internal memory — Storage capacity: 32 GB
- Storage medium Internal memory: Memory capacity (additional information)separate phases: 22000 data records, summarised phases: 38000 data records
- Storage medium Internal memory — Storage interval from: 1 s
- Storage medium Internal memory — Storage interval to: 60 min.
- Storage medium Internal memory: Current consumption current clamp 100 mA DC
- Storage medium Internal memory: Maximum cable diameter 149 mm
- Storage medium Internal memory: Safety standard CAT III 300V
- Storage medium Internal memory: Fuse(s)1000 V, 250 mA, FF
- Storage medium Internal memory: Max. power-off capacity 100 kA
- Storage medium Internal memory — Menu language: German, English (GB), English, Spanish, French
- Storage medium Internal memory — Protection class (device): IP40
- Storage medium Internal memory — Power supply: 100 … 240 V 50/60 Hz (+/- 10%)
- (between neutral conductor and phase A) — (Rechargeable) battery: 1 x 3 V CR 2032 (button cell 3V) , Lithium-ion manganese oxide
- (between neutral conductor and phase A) — Capacity: 245 mAh
- (between neutral conductor and phase A): Performance 0,735 Wh
- (between neutral conductor and phase A) — Operating conditions: -5 … 40 °C , 0 … 80 % RH
- (between neutral conductor and phase A) — Storage conditions: -5 … 40 °C , 0 … 80 % RH
- (between neutral conductor and phase A) — Dimensions: ( L x W x H )123 x 96 x 36 mm
- (between neutral conductor and phase A) — Weight: 202 g
Delivery scope
- 1 x PCE-PA 6500 F150 Power Quality Analyser / Power Analyzer
- 4 x test leads (blue, brown, black, grey) 2 m
- 3 x Rogowski coils
- 3 x magnetic measuring adaptors 6.6 mm
- 1 x blue crocodile clip
- 1 x user manual