Kuma tee 4, Peetri, Estonia
Mon–Fri 9:00 a.m.–5:00 p.m.

Pramac GSW-80I diesel generator

Model: Pramac GSW-80I. Frequency: 50 Hz.

  • In stock
Free shipping For orders over €250
14-Day Return Policy Worry-Free Right to Purchase
Safe Payment
Weight (kg) 1115
Ingress protection rating IP 23
Dimensions 2200 x 1000 x 1743 mm
Tank capacity (L) 240
Power supply 400 V / 3 ph / 50 Hz
Power (kW) 59.42

Model: Pramac GSW-80I

Main features

  • Frequency: 50 Hz
  • Voltage: 400 V
  • Power factor: 0.8 cos ϕ
  • Phase: 3

Power rating

  • Emergency standby power esp: 81.70 kVA
  • Emergency standby power esp: 65.36 kW
  • Prime power prp: 74.28 kVA
  • Prime power prp: 59.42 kW

Rating definitions

Ratings definition (ISO-8528-1)

ESP

  • Emergency Standby Power:

It is the maximum power available during a variable electrical power sequence, under the stated operating conditions, for which a generating set is capable of delivering in the event of a utility power outage or under test conditions for up to 200 h of operation per year with the maintenance intervals and procedures being carried out as prescribed by the manufacturers. The permissible average power output over 24 h of operation shall not exceed 70 % of the ESP.

PRP

  • Prime Power: It is defined as being the maximum power which a generating set is capable of delivering continuously whilst supplying a variable electrical load when operated for an unlimited number of hours per year under the agreed operating conditions with the maintenance intervals and procedures being carried out as prescribed by the manufacturer. The permissible average power output over 24 h of operation shall not exceed 70 % of the prime power.

Engine specifications

  • Engine brand: FPT
  • Model: NEF45SM2A
  • [50hz] exhaust emission level: Stage II
  • Engine cooling system: Water
  • Nr. of cylinder and disposition: 4 in line
  • Displacement: 4500 cm³
  • Aspiration: Turbocharged
  • Speed governor: Mechanical
  • Prime gross power prp: 67.4 kW
  • Maximum gross power ltp esp: 74 kW
  • Oil capacity: 12.8 l
  • Lube oil consumption prp (max): 0.1 %
  • Coolant capacity: 18.5 l
  • Fuel: Diesel
  • Specific fuel consumption 75% prp: 212.1 g/kWh
  • Specific fuel consumption prp: 214.1 g/kWh
  • Starting system: Electric
  • Starting engine capability: 3 kW
  • Electric circuit: 12 V

Engine equipment

  • Starting system: Standards ISO 8528 standard certification of excellent performance related to load acceptance. Injection system The system, is based on direct fuel injection for accurate fuel delivery and is consistent with standard andalternative fuels. Air handling NEF series engines are available in Naturally Aspirated, turbocharged and turbocharged with aftercoolerversions in order to reach the highest engine performance in terms of load acceptance & fuel consumption. 600h Oil interval change NEF series adopt combustion chambers optimized to reduce oil dilution and are designed with anoptimum engine design in terms of mechanical clearances, piston rings and engine oil system calculation. Engine design Balancer counterweights incorporated in crankshaft webs, rear gear train layout, camshaft in crankcase,suspended oil pan, ladder frame cylinder block

Alternator specifications

  • Alternator: Mecc Alte
  • Model: ECP32 1L/4C
  • Voltage: 400 V
  • Frequency: 50 Hz
  • Power factor: 0.8 cos ϕ
  • Poles: 4
  • Type: Brushless
  • Voltage tolerance: 1 %
  • Efficiency @ 75% load: 91 %
  • Class: H
  • Ip protection: 23

Alternator equipment

  • Mechanical structure: Mechanical structure
  • Mechanical structure text: Robust mechanical structure which permits easy access to the connections and components during routine maintenance check-ups.
  • Voltage regulator: Voltage regulator
  • Voltage regulator text: Voltage regulation with DSR. The digital DSR controls the range of voltage, avoiding any possible trouble that can be made by unskilled personnel. The voltage accuracy is ±1% in static condition with any power factor and with speed variation between 5% and +30% with reference to the rated speed.
  • Windings / excitation system: Windings / Excitation system
  • Windings / excitation system text: Generator stator is wound to 2/3 pitch. This eliminates triplen (3rd, 9th, 15th …) harmonics on the voltage waveform and is found to be the optimum design for trouble-free supply of non-linear loads. The 2/3 pitch design avoids excessive neutral currents sometimes seen with higher winding pitches. MAUX  (Standard): The MAUX MeccAlte Auxiliary Winding is a separate winding within the main stators that feeds the regulator. This winding enables to take an overload of 300% forced current (short circuit maintenance) for 20 seconds. This is ideal for motor starting requirements.
  • Insulation / impregnation: Insulation / Impregnation
  • Insulation / impregnation text: Insulation is of class H standard. Impregnation is made with premium tropicalised epoxy resins by dipping and dripping. High voltage parts are impregnated by vacuum, so the insulation level is always very good. In the high-power models, the stator windings undergo a second insulation process. Grey protection is applied on the main and exciter stator to give enhanced protection.
  • Reference standards: Reference standards
  • Reference standards text: Alternator manufactured according to , and complies with , the most common specification such as CEI 2-3, IEC 34-1, EN 60034-1, VDE 0530, BS 4999-5000, CAN/CSA-C22.2 No14-95-No100-95.

Genset equipment

BASE FRAME MADE OF WELDED STEEL PROFILE, COMPLETE WITH:

• Steel base frame with support legs

• Anti-vibration mountings properly sized

• Grounding point to connect all metal parts of the generating set

PROTECTIONS: • Moving and rotating parts protection against accidental contacts. ENGINE COMPLETE WITH: • Battery • Liquids (no fuel)

EXHAUST (Standard): • Industrial silencer (loose)

  • Baseframe: FUEL TANK WITH THE FOLLOWING COMPONENT: • Filler neck • Air breather (ventilation pipe) • Minimum fuel level sensor

Dimensional data

  • Length: 2200 (L) mm
  • Width: 1000 (W) mm
  • Height: 1743 (H) mm
  • Dry weight: 1115 kg
  • Fuel tank capacity: 240 l
  • Fuel tank material: Metal

Autonomy

  • Fuel consumption @ 75% prp: 12.69 l/h
  • Fuel consumption @ 100% prp: 17.18 l/h
  • Running time 75% prp: 18.91 h
  • Running time 100% prp: 13.97 h

Installation data

  • Total air flow: 152.50 m³/min
  • Exhaust gas flow: 9.2 m³/min
  • Exhaust gas temperature: 525 °C

Electrical data

  • Battery capacity: 92 Ah
  • Max current: 117.93 A
  • Circuit breaker: 125 A

Control panel availability

  • Automatic control panel: ACP

Acp – automatic control panel

Mounted on the genset, complete with digital control unit for monitoring, control and protection of the generating set.

DIGITAL INSTRUMENTATION (through AC-03)

• Generating set voltage (3 phases).
• Mains voltage.
• Generating set frequency.
• Generating set current (3 phases).
• Battery voltage.
• Power (kVA – kW – kVAr).
• Power factor Cos φ.
• Hours-counter.
• Engine speed r.p.m.
• Fuel level (%).
• Engine temperature (depending on model)

  • Second part of the text: COMMANDS AND OTHERS • Four operation modes: OFF – Manual starting – Automatic starting – Automatic test. • Pushbutton for forcing Mains contactor or Genset contactor. • Push-buttons: start/stop, fault reset, up/down/page/enter selection. • Remote starting availability. • DC system disconnection switch. • Acoustic alarm. • Automatic battery charger. • RS232 Communication port. • Settable PASSWORD for protection level.
  • Third part of the text: PROTECTIONS WITH ALARM • Engine protections: low fuel level, low oil pressure, high engine temperature. • Genset protections: under/over voltage, overload, under/over frequency, starting failure, under/over battery voltage PROTECTIONS WITH SHUTDOWN • Engine protections: low fuel level, low oil pressure, high engine temperature, • Genset protection: under/over voltage, overload, under/over battery voltage, battery charger failure. • Circuit breaker protection: III poles. • Earth Fault included in the control unit.
  • Part4: OTHERS PROTECTIONS • Emergency stop button.

Out put panel acp

  • Plinth row for connection from acp to lts panel.: √
  • Power cables connection to circuit breaker.: √

Optional features:

  • To be ordered with equipment (when necessary): :

Engine supplements

  • Coolant pre-heating system: PHS

Datasheet (PDF)