Model: Pramac GBW-22Y (ALT. M)
Main features
- Frequency: 50 Hz
- Voltage: 400 V
- Power factor: 0.8 cos ϕ
- Phase: 3
Power rating
- Emergency standby power esp: 19.25 kVA
- Emergency standby power esp: 15.40 kW
- Prime power prp: 18.27 kVA
- Prime power prp: 14.62 kW
Rating definitions
Ratings definition (ISO-8528-1)
ESP
- Emergency Standby Power:
It is the maximum power available during a variable electrical power sequence, under the stated operating conditions, for which a generating set is capable of delivering in the event of a utility power outage or under test conditions for up to 200 h of operation per year with the maintenance intervals and procedures being carried out as prescribed by the manufacturers. The permissible average power output over 24 h of operation shall not exceed 70 % of the ESP.
PRP
- Prime Power: It is defined as being the maximum power which a generating set is capable of delivering continuously whilst supplying a variable electrical load when operated for an unlimited number of hours per year under the agreed operating conditions with the maintenance intervals and procedures being carried out as prescribed by the manufacturer. The permissible average power output over 24 h of operation shall not exceed 70 % of the prime power.
Engine specifications
- Engine brand: Yanmar
- Model: 4TNV88-BGPGEC
- [50hz] exhaust emission level: Stage II
- Engine cooling system: Water
- Nr. of cylinder and disposition: 4 in line
- Displacement: 2190 cm³
- Aspiration: Natural
- Speed governor: Mechanical
- Prime gross power prp: 17.3 kW
- Maximum gross power ltp esp: 18.2 kW
- Oil capacity: 7.4 l
- Coolant capacity: 2.7 l
- Fuel: Diesel
- Specific fuel consumption 75% prp: 245 g/kWh
- Specific fuel consumption prp: 245 g/kWh
- Starting system: Electric
- Starting engine capability: 1.4 kW
- Electric circuit: 12 V
Engine equipment
- Starting system: Engine Equipment Standards The above ratings represent the engine performance capabilities to conditions specified in ISO 8528/1, ISO 3046/1:1986, BS 5514/1 Fuel system • Direct injection system • Fuel filter paper element • Fuel pump Bosch in-Line Lube oil system • Forced feed system • Trochoid pump • Paper element lube oil filter Induction system • Mounted air filter Cooling system • Thermostatically-controlled system with gear-driven circulation pump and belt-driven pusher fan • Mounted radiator and piping
Alternator specifications
- Alternator: Mecc Alte
- Model: ECP28-M4 C
- Voltage: 400 V
- Frequency: 50 Hz
- Power factor: 0.8 cos ϕ
- Poles: 4
- Type: Brushless
- Voltage tolerance: 1 %
- Efficiency @ 75% load: 88,2 %
- Class: H
- Ip protection: 23
Alternator equipment
- Mechanical structure: Mechanical structure
- Mechanical structure text: Robust mechanical structure which permits easy access to the connections and components during routine maintenance check-ups.
- Voltage regulator: Voltage regulator
- Voltage regulator text: Voltage regulation with DSR. The digital DSR controls the range of voltage, avoiding any possible trouble that can be made by unskilled personnel. The voltage accuracy is ±1% in static condition with any power factor and with speed variation between 5% and +30% with reference to the rated speed.
- Windings / excitation system: Windings / Excitation system
- Windings / excitation system text: Generator stator is wound to 2/3 pitch. This eliminates triplen (3rd, 9th, 15th …) harmonics on the voltage waveform and is found to be the optimum design for trouble-free supply of non-linear loads. The 2/3 pitch design avoids excessive neutral currents sometimes seen with higher winding pitches. MAUX (Standard): The MAUX MeccAlte Auxiliary Winding is a separate winding within the main stators that feeds the regulator. This winding enables to take an overload of 300% forced current (short circuit maintenance) for 20 seconds. This is ideal for motor starting requirements.
- Insulation / impregnation: Insulation / Impregnation
- Insulation / impregnation text: Insulation is of class H standard. Impregnation is made with premium tropicalised epoxy resins by dipping and dripping. High voltage parts are impregnated by vacuum, so the insulation level is always very good. In the high-power models, the stator windings undergo a second insulation process. Grey protection is applied on the main and exciter stator to give enhanced protection.
- Reference standards: Reference standards
- Reference standards text: Alternator manufactured according to , and complies with , the most common specification such as CEI 2-3, IEC 34-1, EN 60034-1, VDE 0530, BS 4999-5000, CAN/CSA-C22.2 No14-95-No100-95.
Genset equipment
BASE FRAME MADE OF WELDER STEEL PROFILE, COMPLETE WITH:
• Anti-vibration mountings properly sized
• Visual fuel level indicator
• Integrated support legs.
OIL DRAININ PIPE WITH CAP: • Oil draining facilities
PROTECTIONS : • Moving and rotating parts protections against accidental contacts ENGINE COMPLETE WITH: • Battery • Liquids (no fuel)
- Baseframe: PLASTIC FUEL TANK, COMPLETE WITH: • Filler neck • Air breather • Fuel refilling
- Text noise: EXHAUST (Standard) : • Industrial silencer
Dimensional data
- Length: 1600 (L) mm
- Width: 870 (W) mm
- Height: 1018 (H) mm
- Dry weight: 456 kg
- Fuel tank capacity: 51 l
- Fuel tank material: Plastic
Autonomy
- Fuel consumption @ 75% prp: 3.78 l/h
- Fuel consumption @ 100% prp: 5.05 l/h
- Running time 75% prp: 13.49 h
- Running time 100% prp: 10.10 h
Installation data
- Total air flow: 58.08 m³/min
- Exhaust gas flow: 3.5 m³/min
- Exhaust gas temperature: 470 °C
Electrical data
- Battery capacity: 70 Ah
- Max current: 27.79 A
- Circuit breaker: 32 A
Control panel availability
- Automatic control panel: ACP
Acp – automatic control panel
Automatic control panel mounted on the genset, complete with digital control unit for monitoring, control and protection of the generating set.
INSTRUMENTATION DIGITAL
• Mains voltage.
• Generating set voltage (3 phases).
• Generating set frequency.
• Generator set current.
• Battery voltage
• Hours-counter.
- Second part of the text: COMMANDS AND OTHERS • Operation modes: OFF – Manual Starting – Automatic Starting. • Push-buttons: start/stop, fault reset, up/down/page/enter selection. • Emergency stop button. • Remote starting availability. • Automatic battery charger. • USB port.
- Third part of the text: PROTECTIONS WITH ALARM • Engine protections: low oil pressure, high engine temperature • Genset protections: under/over voltage, overload, under/over frequency, starting failure, under/over battery voltage, battery charger failure PROTECTIONS WITH SHUTDOWN • Engine protections: low oil pressure, high engine temperature • Genset protection: under/over voltage, overload, under/over battery voltage • Circuit breaker protection: III poles • Differential protection
- Part4: OTHERS • Cover protection Power switch
Out put panel acp
- Plinth row for connection from acp to lts panel.: √
- Power cables connection to circuit breaker.: √
- 3p+n+t cee 400v 32a: 1 [●] n
Optional features:
- To be ordered with equipment (when necessary): :
Engine supplements
- Coolant pre-heating system: PHS