Kuma tee 4, Peetri, Estonia
Mon–Fri 9:00 a.m.–5:00 p.m.

TFV 600 Ex Centrifugal Fan

TFV 600 Ex Centrifugal Fan

The TFV 600 Ex is designed for high flow rates in hazardous areas with high back pressure, even over long transport distances via multiple interconnected air transport hoses.

  • Available for backorder (1–2 weeks)
12 500 price including km
Free shipping For orders over €250
14-Day Return Policy Worry-Free Right to Purchase
Safe Payment

TFV 600 Ex Centrifugal Fan

Proper ventilation is not only important for a pleasant working environment, but is also essential in many areas for occupational safety reasons and in accordance with official regulations.

Ventilating rooms removes harmful substances such as paint and varnish fumes, welding fumes, dust particles, carbon monoxide, nitrogen oxides, carbon dioxide, and water vapor.

The TFV 600 Ex is designed for high flow rates in hazardous areas with high back pressure, even over long transport distances via multiple interconnected air transport hoses.

This makes the TFV 600 Ex the ideal transfer fan for ventilating Class 2 explosion-protected areas, such as during tank cleaning, at port facilities, in refineries, in mines, or in silos.

This powerful radial fan ensures a high airflow even over long hose distances of 50 meters and through multiple bends, because, unlike axial fans, the TFV 600 Ex directs air perpendicular to the impeller shaft using the centrifugal principle, whereby the air is forced outward and compressed within the turbine-shaped housing.

And since the centrifugal fan in this high-quality unit—which is manufactured entirely in Germany and designed in accordance with ATEXDirective 2014/34/EU, is integrated into a robust powder-coated steel housing with a highly durable two-component paint finish, it can also be used in aggressive environments. Optionally, the housing can be supplied in any desired steel grade.

In addition to the standard frameless version, the TFV 600 Ex is also available as an option, as shown, including an additional galvanized steel frame with sturdy transport rollers, forklift slots, and crane lifting corners. The transport frame not only offers you maximum mobility for use in frequently changing locations, but it can also be stacked twice to save space during transport or storage.

TFV 600 Ex switches, cables, and plugs are approved for use in potentially explosive atmospheres. Suitable connectors, approved for use in Zones 1, 2, 21, and 22, are available for extension cables.

An 18.5 kW star-delta contactor combination for the TFV 600 Ex is also available as an option for EX Zone 22, 400 V, AC3, IP 55.

Here are a few of the practical advantages of the TFV 600, in brief:

  • Development, design, manufacturing: 100% Trotec
  • Explosion Protection Group II, Category 3G, Temperature Class 4
  • A robust, high-current, high-quality device “made in Germany.”
  • Splash-proof version (IP55)
  • The fan motor is located outside the main airflow
  • Can be connected to both intake and exhaust ducts
  • Stable regions of the characteristic curve and consistently high pressure
  • Also available optionally for Explosion Protection Group II, Category 2G (Zone 1), Category 2D (Zone 21), and Category 3D (Zone 2).

Explosion protection refers to protection against explosions and their effects. Its purpose is to prevent damage caused by systems, technical products, and the like. Explosion protection encompasses legal provisions such as the European Union’s ATEX directives. Important: Please ask our service staff about the use of explosion-proof fans!

Please note that the shipping frame shown in the product image is not included in the package, but is available as an accessory!

Price for the frame: 2,300 euros, including installation.

Air volume
Max – free outlet [m³/h] 16,000
air volume at atmospheric pressure
m³/h 10,000
Pa 4,000
airflow
while blowing out
sucking
air discharge velocity
Ms. 21
km/h 75.6
fan
fan speeds 1
air pressure
Maximum level [Pa] 4900
conveyor temperature
maximum [°C] 80
Environmental Conditions
Temperature range min [°C] -20
Maximum temperature range [°C] 40
security feature
IP Protection Class 55
electrical values
Power connection 400 V/50 Hz
Power consumption [kW] 18.5
Recommended protection [A] 32
Rated Current [A] 32
electrical connection
plug plug CEE 63 A
cable length [m]
hose connection
Inlet manifold [mm] 600
outlet nozzle [mm] 450
sound levels
Distance 1 m [dB(A)] 84
Distance 3 m [dB(A)] 78
explosion protection
Zone 2
protection class II 3G, T4
Dimensions
Length (without packaging) [mm] 1,305
Width (without packaging) [mm] 1250
Height (without packaging) [mm] 1170
Weight
(without packaging) [kg] 233
EQUIPMENT, FEATURES, AND FUNCTIONS
Material
Steel, powder-coated

FAQ