Model: Pramac GSW-470P
Main features
- Frequency: 50 Hz
- Voltage: 400 V
- Power factor: 0.8 cos ϕ
- Phase: 3
Power rating
- Emergency standby power esp: 462.91 kVA
- Emergency standby power esp: 370.33 kW
- Prime power prp: 410.88 kVA
- Prime power prp: 328.70 kW
Rating definitions
Ratings definition (ISO-8528-1)
ESP
- Emergency Standby Power:
It is the maximum power available during a variable electrical power sequence, under the stated operating conditions, for which a generating set is capable of delivering in the event of a utility power outage or under test conditions for up to 200 h of operation per year with the maintenance intervals and procedures being carried out as prescribed by the manufacturers. The permissible average power output over 24 h of operation shall not exceed 70 % of the ESP.
PRP
- Prime Power: It is defined as being the maximum power which a generating set is capable of delivering continuously whilst supplying a variable electrical load when operated for an unlimited number of hours per year under the agreed operating conditions with the maintenance intervals and procedures being carried out as prescribed by the manufacturer. The permissible average power output over 24 h of operation shall not exceed 70 % of the prime power.
Engine specifications
- Engine brand: Perkins
- Model: 2206A-E13TAG3
- [50hz] exhaust emission level: Non Emission Certified
- Engine cooling system: Water
- Nr. of cylinder and disposition: 6 in line
- Displacement: 12500 cm³
- Aspiration: Turbocharged
- Speed governor: Electronic
- Prime gross power prp: 368.4 kW
- Maximum gross power ltp esp: 412.5 kW
- Oil capacity: 40 l
- Lube oil consumption prp (max): 0.1 %
- Coolant capacity: 51.4 l
- Fuel: Diesel
- Specific fuel consumption 75% prp: 199 g/kWh
- Specific fuel consumption prp: 197 g/kWh
- Starting system: Electric
- Starting engine capability: 7.8 kW
- Electric circuit: 24 V
Engine equipment
- Starting system: Cooling system • Gear-driven circulating pump • Mounted belt-driven pusher fan • Radiator incorporating air-to-air charge cooler, (supplied loose) • System designed for ambients up to 50ºC (122ºF) Electrical equipment • 3 level engine protection system •2 4 volt starter motor and 24 volt 70 amp alternator with DC output Fuel system • Fuel cooler • Governing to ISO 8528-5 class G2 with isochronous capability •Mechanically actuated electronically controlled unit fuel injectors with full authority electronic control • Replaceable ‘Ecoplus’ fuel filter elements with primary filter/water separator Oil system • Full-flow replaceable ‘Ecoplus’ filter • Oil cooler integral with filter header • Wet sump with filler and dipstick
Alternator specifications
- Alternator: Mecc Alte
- Model: ECO40 2S4 C
- Voltage: 400 V
- Frequency: 50 Hz
- Power factor: 0.8 cos ϕ
- Poles: 4
- Type: Brushless
- Voltage tolerance: 1 %
- Efficiency @ 75% load: 94.6 %
- Class: H
- Ip protection: 23
Alternator equipment
- Mechanical structure: Mechanical structure
- Mechanical structure text: Robust mechanical structure which permits easy access
to the connections and components during routine maintenance check-ups. - Voltage regulator: Voltage regulator
- Voltage regulator text: Voltage regulation with DER 1. The
digital DER 1 is a Digital controlled regulator, based on DSP (Digital Signal
Processor) that combines function as Voltage Regulation and Alternator
Protections and Diagnostic into a very small single board. Voltage supply: 40Vac÷270Vac Maximum continuous output current:
4Adc Frequency range: 12Hz÷72Hz Single phase sensing automatic
recognition Average value of voltage
regulation Voltage regulation range (sensing)
from 75Vac to 300Vac Precision of voltage regulation: ±
1% from no-load to nominal load in static condition, with any power factor and
for frequency variations ranging from -5% to +20% of the nominal value. Precision of voltage regulation: ±
0,5% in stabilized conditions (load, temperature). Transient voltage drop and
overvoltage within ± 15% Voltage recovery time within ± 3%
of the value set, in less than 300 msec. Underspeed protection with
adjustable threshold and slope Overvoltage and undervoltage
alarms Excitation overcurrent protection
with delayed intervention Alarm conditions storage (type of
alarm, number of events, duration of the last event, total time) Memorization of the regulator
operation time - Windings / excitation system: Windings / Excitation system
- Windings / excitation system text: Generator stator is wound
to 2/3 pitch. This eliminates triple (3rd, 9th, 15th …) harmonics on the
voltage waveform and is found to be the optimum design for trouble-free supply
of non-linear loads. The 2/3 pitch design avoids excessive neutral currents
sometimes seen with higher winding pitches. MAUX (Standard): The MAUX
MeccAlte Auxiliary Winding is a separate winding within the main stators that
feeds the regulator. This winding enables to take an overload of 300% forced
current (short circuit maintenance) for 20 seconds. This is ideal for motor
starting requirements. PMAUX (optional): Alternator can be equipped with the
optional PMAUX (Permanent Magnet Generator) which matches the performance and
is capable of supporting both linear and distorted loads. - Insulation / impregnation: Insulation / Impregnation
- Insulation / impregnation text: Insulation
is of class H standard. Impregnation is made with premium tropicalised epoxy
resins by dipping and dripping. High voltage parts are impregnated by vacuum,
so the insulation level is always very good. In the high-power models, the
stator windings undergo a second insulation process. Grey protection is applied
on the main and exciter stator to give enhanced protection. - Reference standards: Reference standards
- Reference standards text: Alternator
manufactured according to , and complies with , the most common specification
such as CEI 2-3, IEC 34-1, EN 60034-1, VDE 0530, BS 4999-5000, CAN/CSA-C22.2
No14-95-No100-95
Genset equipment
BASE FRAME MADE OF WELDED STEEL PROFILE, COMPLETE WITH:
• Anti-vibration mountings properly sized
• Screwed support legs.
ENGINE COMPLETE WITH: • Battery • Liquids (no fuel)
CANOPY : • Soundproof canopy made up of modular panels, realized with zinced steel as treatment against corrosion and aggressive conditions, properly fixed and sealed allowing a full weatherproof enclosure. • Easy access to the genset for maintenance purposes thanks to: Wide lateral access doors fixed by stainless steel hinges and provided with plastic lockable handles and internal perforated galvanized steel-sheet; Detachable panels, with screws holes protected by rubber tap. • Control panel protection door provided with suitable window and lockable handle. • Lateral air inlet opening properly protected and soundproofed. Exhaust air outlet from the roof, trough wet section protected by proper grid. • Double lifting points frame structure.
- Baseframe: METAL FUEL TANK WITH THE FOLLOWING COMPONENT: • Filler neck • Air breather (ventilation pipe) • Minimum fuel level sensor
- Text noise: SOUNDPROOF : • Noise attenuation thanks to soundproofing material • Efficient residential silencer placed inside the canopy
Dimensional data
- Length: 4400 (L) mm
- Width: 1560 (W) mm
- Height: 2250 (H) mm
- Fuel tank capacity: 720 l
- Fuel tank material: Metal
Autonomy
- Fuel consumption @ 75% prp: 66.52 l/h
- Fuel consumption @ 100% prp: 86.40 l/h
- Running time 75% prp: 10.82 h
- Running time 100% prp: 8.33 h
Noise level
- Guaranteed noise level (lwa): 97 dB(A)
- Noise pressure level @ 7 m: 67 dB(A)
Installation data
- Total air flow: 732.30 m³/min
- Exhaust gas flow: 64.6 m³/min
- Exhaust gas temperature: 630 °C
Electrical data
- Max current: 668.18 A
- Circuit breaker: 800 A
Control panel availability
- Automatic control panel: ACP
Acp – automatic control panel
Mounted on the genset, complete with digital control unit for monitoring, control and protection of the generating set protected through door with lockable door
INSTRUMENTATION DIGITAL
• Generating set voltage (3 phases)• Mains voltage
• Generating set frequency
• Generating set current (3 phases)
• Battery voltage• Power (kVA – kW – kVAr)• Power factor Cos• Hours-counter
• Engine speed r.p.m.• Fuel level (%)• Engine temperature (depending on model)
- Second part of the text: COMMANDS AND OTHERS • Four operation modes: OFF – Manual starting – Automatic starting – Automatic test • Pushbutton for forcing Mains contactor or Genset contactor • Push-buttons: start/stop, fault reset, up/down/page/enter selection • Remote starting availability • Acoustic alarm • Automatic battery charger • USB, RS232 and RS485 Communication ports • Settable PIN for protection level
- Third part of the text: PROTECTIONS WITH ALARM • Engine protections: low fuel level, low oil pressure, high engine temperature • Genset protections: under/over voltage, overload, under/over frequency, starting failure, under/over battery voltage PROTECTIONS WITH SHUTDOWN • Engine protections: low fuel level, low oil pressure, high engine temperature • Genset protection: under/over voltage, overload, under/over battery voltage, battery charge failure
- Part4: OTHERS PROTECTIONS • Emergency stop button
Out put panel acp
- Predisposed for remote control optional:: RCG
- External terminal board (etb): Standard
Optional features:
- To be ordered with equipment (when necessary): :
Engine supplements
- Coolant pre-heating system: PHS