The GDW series covers a power range from 10 to 820kVA Standby. It is designed for Emergency Standby and Continuous Power applications, with a modular design offering flexibility in the scope of supply and a wide range of mechanical and electrical options. The series is available in Open, Silent and Extra Silent versions to meet global requirements and specific local needs.
The GDW series is designed for emergency standby and continuous power applications, including hospitals, data centers, retail, Oil & Gas, mining, power plant production and water treatment. The series is available in three versions: Open, Silenced Enclosure and Extra Silenced Enclosure. Each version has a sturdy design with a robust structure and enclosure. Large control and power sections meet power plant requirements. The modular design has a basic core configuration compatible with a wide range of modules to cover stationary application needs.
Video: GDW video
Power ratings
Ratings definition (ISO-8528-1): ESP (Emergency Standby Power) is the maximum power available during a variable electrical power sequence, under the stated operating conditions, that a generating set can deliver in the event of a utility power outage or under test conditions for up to 200 h of operation per year, with the maintenance intervals and procedures prescribed by the manufacturer being carried out. The permissible average power output over 24 h of operation shall not exceed 70 % of the ESP.
PRP (Prime Power) is the maximum power a generating set can deliver continuously while supplying a variable electrical load, when operated for an unlimited number of hours per year under the agreed operating conditions and with the maintenance intervals and procedures prescribed by the manufacturer being carried out. The permissible average power output over 24 h of operation shall not exceed 70 % of the prime power.
G2 class load acceptance in accordance with ISO 8528-5. Higher performance classes are available on request.
Technical specifications
| Model | GDW_280V/FS2 |
|---|---|
| Fuel | Diesel |
| Emergency standby power (ESP) | 275.0 kVA |
| Emergency standby power (ESP) | 220.0 kW |
| Prime power (PRP) | 250.0 kVA |
| Prime power (PRP) | 200.0 kW |
| Voltage | 400/230 V |
| Frequency | 50 Hz |
| Power factor | cos ϕ 0.8 |
| Phases | 3 |
| Load acceptance | G2 class, in accordance with ISO 8528-5 |
| Engine brand | Volvo |
| Engine model | TAD841GE |
| Nominal engine speed | 1500 rpm |
| Engine cooling system | Water |
| Exhaust emission level | Stage II |
| Number and arrangement of cylinders | 6 in line |
| Displacement | 7700 cm³ |
| Aspiration type | Turbocharged |
| Speed governor | Electronic |
| Gross engine power (ESP) | 254 kWm |
| Gross engine power (PRP) | 232 kWm |
| Fan power | 12 kWm |
| Fan air flow | 294 m³/min |
| Total oil capacity | 27 l |
| Total coolant capacity | 36 l |
| Specific fuel consumption at 100% ESP | 198 g/kWh |
| Specific fuel consumption at 75% PRP | 204 g/kWh |
| Starting system | Electric |
| Electric circuit | 24 V |
| Alternator brand | Mecc Alte |
| Alternator model | ECO38 2M4 C |
| Winding | Standard |
| Winding connections | Series Star |
| Alternator frequency | 50 Hz |
| Alternator voltage | 400 V |
| Alternator phases | 3 |
| Alternator power factor | cos ϕ 0.8 |
| Stand-by rating at 27°C | 275 kVA |
| Continuous nominal rating at 40°C | 250 kVA |
| Efficiency at 100% load | 93.4 % |
| Alternator type | Brushless |
| Poles | 4 |
| Voltage tolerance | 1 % |
| Insulation class | H |
| IP protection | 23 |
| Total air flow | 342 m³/min |
| Exhaust gas flow at PRP | 42 m³/min |
| Exhaust gas temperature | 478 °C |
| Fuel consumption at 75% PRP | 41.79 l/h |
| Fuel consumption at 100% PRP | 53.30 l/h |
| Battery voltage | 24 V |
| Gen-set voltage | 400/230 V |
| Maximum current | 397 A |
| Nominal current | 361 A |
| Circuit breaker | 400 A |
| Automatic control panel | Auto Mains Failure (AMF) function; gen-set controller for a single genset operating in standby or prime power modes; full gen-set monitoring and protection; detailed event and performance log with time and date; a wide range of remote control modules available as an option; a wide range of I/O expansion modules available as an option; power supply by circuit breaker and/or terminal bus bar |
| Open version | Baseframe made of welded steel profile; properly sized anti-vibration mountings; screwed support legs; hole for handling by crane; protection against accidental contact with moving and rotating parts; grounding point to connect all metal parts to ground |
| Open version dimensions (L × W × H) | 3055 × 1200 × 1795 mm |
| Open version weight | 2033 kg |
| Open version option | Residential Exhaust System (RES) |
| Canopy version | Weatherproof enclosure made of galvanized sheet metal protects the genset from corrosion and aggressive conditions. The soundproofed enclosure, with high-quality soundproof material and a residential silencer, allows a low noise emission level. Large lateral doors allow easy service and maintenance. Doors have key-lockable handles. Baseframe made of welded steel profile; properly sized anti-vibration mountings; screwed support legs; hole for handling by crane; protection against accidental contact with moving and rotating parts; grounding point to connect all metal parts to ground. |
| Canopy version dimensions (L × W × H) | 3702 × 1200 × 2050 mm |
| Canopy version weight | 2563 kg |
| Guaranteed noise level (LWA), canopy version | 97 dB(A) |
| Noise pressure level at 1 m, canopy version | 78 dB |
| Noise pressure level at 7 m, canopy version | 68 dB |
| Canopy version option | Roof lifting point (RLP) |
| Optional fuel tanks | To be ordered with the equipment when necessary. |
| MFT-XS running time at 75% PRP | 11.96 h |
| MFT-XS fuel tank capacity and location | 500 l; internal |
| MFT-S running time at 75% PRP | 14.36 h |
| MFT-S fuel tank capacity and location | 600 l; internal |
| MFT-M running time at 75% PRP | 23.93 h |
| MFT-M fuel tank capacity and location | 1000 l; with sub-base |
| MFT-M EXTRA length | 647 mm (open versions only) |
| MFT-M EXTRA height | 340 mm (open/canopy versions) |
| MFT-M EXTRA weight | 548 kg |
| MFT-L running time at 75% PRP | 52.64 h |
| MFT-L fuel tank capacity and location | 2200 l; with sub-base |
| MFT-L EXTRA length | 647 mm (open versions only) |
| MFT-L EXTRA height | 655 mm (open/canopy versions) |
| MFT-L EXTRA weight | 826 kg |
| Optional features | To be ordered with the equipment when necessary: Pre-Heating System (PHS); Manual battery switch (MBS); Air Shut-Off Valve (ASV); Heavy-Duty Air Filter (HDF); Water Separator Filter (WSP); Winding Total Protection (WTP); Alternator anti-condensation heater (ACH); Galvanized skid base with fork lift point (GSB) |
| Use and maintenance manual | 94367; English version [EN] |